General Features
No. of Phases: 3
Rated voltage: 480V
Rated frequency: 60 Hz
Requirements: THDv ≤ 2%, line voltage unbalance ≤ 1%
THDi: 5% lower @ rated load
Overload capacity: 160% for 60 seconds, once per hour
Load Description: Symmetrical converter load with an uncontrolled B6-type rectifier
Electrical Specifications
Model: PFH-150-480-17 PFH-200-480-17
VFD Rated Load: 150–200 HP
Power Loss: 1,187 W (Model PFH-150-480-17) – 1,566 W (Model PFH-200-480-17)
Physical Characteristics
Weight: 189 kg (Model PFH-150-480-17) – 222 kg (Model PFH-200-480-17)
Dimensions: 480x950x440 (Model PFH-150-480-17) – 480x950x480 (Model PFH-200-480-17)
Construction Features
Test voltage: 3 kV for 10 seconds
Insulation class: H
Noise level: less than 65 dB
Enclosure: IP00
Insulation resistance: greater than 100 MΩ (1000 Vdc)
Ambient temperature: -25°C to 45°C
Temperature increase constant: K minus 110
Standard:
- IEEE 519
- EN 61000-2-2
- EN 61000-2-4
- IEC/EN 61000-3-2
- IEC/EN 61000-3-4
- IEC/61000-3-12